ConditionScreenings bin overfilling at weekends.
Corrective actionAdd a Saturday empty to the rota.
Latest update · Sep 30, 2026 · GuestSaturday empty added.
Exec Office · Tamarind Point Utility Company
Corrective actions from the plant reviews, the required testing countdown and the latest water quality results. Changes are counted since Quarterly plant review (Sep 21, 2026).
| Plant | Complete | In Progress | Noted | Open | Total | % Complete |
|---|---|---|---|---|---|---|
| Drinking Water Plant (RO Plant) | 2 | 2 | 0 | 2 | 6 | 33% |
| Wastewater Plant | 3 | 1 | 1 | 1 | 6 | 50% |
| Both plants | 5 | 3 | 1 | 3 | 12 | 42% |
| Party | Complete | Total | % Complete |
|---|---|---|---|
| Island Water | 3 | 7 | 43% |
| TPU | 2 | 4 | 50% |
| Island Water / TPU | 0 | 1 | 0% |
Since the last review: 9 updated · 9 with a response on file · 3 still awaiting any response.
Mon Nov 2, 2026 · Island Water lab · Tank outlet
| Parameter | Result | Limit | |
|---|---|---|---|
| Free chlorine | 1.27 mg/L | 0.2 – 4.0 | ✓ Within |
| Total chlorine | 1.09 mg/L | ≤ 4.0 | ✓ Within |
| pH | 7.2 | 6.5 – 8.5 | ✓ Within |
| Turbidity | 0.13 NTU | ≤ 1.0 | ✓ Within |
| TDS | 288 mg/L | ≤ 500 | ✓ Within |
| Conductivity | 402 µS/cm | ||
| Total coliform | Absent per 100 mL | Absent | ✓ Within |
| E. coli | Absent per 100 mL | Absent | ✓ Within |
Mon Nov 2, 2026 · Island Water lab · Effluent to pond
| Parameter | Result | Limit | |
|---|---|---|---|
| BOD5 | 10 mg/L | ≤ 30 | ✓ Within |
| TSS | 9 mg/L | ≤ 30 | ✓ Within |
| pH | 7.1 | 6.0 – 9.0 | ✓ Within |
| Ammonia (NH3-N) | 0.8 mg/L | ||
| Total nitrogen | 6.5 mg/L | ||
| Total phosphorus | 2.1 mg/L | ||
| Fecal coliform | 138 per 100 mL | ||
| Turbidity | 2.10 NTU |
Headworks
ConditionScreenings bin overfilling at weekends.
Corrective actionAdd a Saturday empty to the rota.
Latest update · Sep 30, 2026 · GuestSaturday empty added.
Aeration
ConditionBlower 2 running hot; filter dirty.
Corrective actionClean the intake filter and log blower temperatures weekly.
Latest update · Oct 1, 2026 · GuestFilter cleaned; temperatures logged weekly.
ConditionDissolved oxygen probe reading low against the hand meter.
Corrective actionCalibrate the probe and replace the membrane cap.
Latest update · Oct 2, 2026 · GuestProbe calibrated; new cap on order.
Clarifier
ConditionScum baffle bracket corroded.
Corrective actionReplace the bracket with stainless.
Latest updateNo response recorded yet.
Disinfection
ConditionTwo UV lamps past their rated hours.
Corrective actionReplace the lamps and record the hours.
Latest update · Oct 4, 2026 · GuestLamps ordered with the quarterly parts.
Effluent
ConditionFence gate does not latch.
Corrective actionFix the latch and add a sign.
Latest update · Oct 5, 2026 · GuestLatch fixed and sign up.