ConditionScum baffle bracket corroded.
Corrective actionReplace the bracket with stainless.
Latest updateNo response recorded yet.
Exec Office · Tamarind Point Utility Company
Corrective actions from the plant reviews, the required testing countdown and the latest water quality results. Changes are counted since Quarterly plant review (Sep 21, 2026).
| Plant | Complete | In Progress | Noted | Open | Total | % Complete |
|---|---|---|---|---|---|---|
| Drinking Water Plant (RO Plant) | 2 | 2 | 0 | 2 | 6 | 33% |
| Wastewater Plant | 3 | 1 | 1 | 1 | 6 | 50% |
| Both plants | 5 | 3 | 1 | 3 | 12 | 42% |
| Party | Complete | Total | % Complete |
|---|---|---|---|
| Island Water | 3 | 7 | 43% |
| TPU | 2 | 4 | 50% |
| Island Water / TPU | 0 | 1 | 0% |
Since the last review: 9 updated · 9 with a response on file · 3 still awaiting any response.
Mon Nov 2, 2026 · Island Water lab · Tank outlet
| Parameter | Result | Limit | |
|---|---|---|---|
| Free chlorine | 1.27 mg/L | 0.2 – 4.0 | ✓ Within |
| Total chlorine | 1.09 mg/L | ≤ 4.0 | ✓ Within |
| pH | 7.2 | 6.5 – 8.5 | ✓ Within |
| Turbidity | 0.13 NTU | ≤ 1.0 | ✓ Within |
| TDS | 288 mg/L | ≤ 500 | ✓ Within |
| Conductivity | 402 µS/cm | ||
| Total coliform | Absent per 100 mL | Absent | ✓ Within |
| E. coli | Absent per 100 mL | Absent | ✓ Within |
Mon Nov 2, 2026 · Island Water lab · Effluent to pond
| Parameter | Result | Limit | |
|---|---|---|---|
| BOD5 | 10 mg/L | ≤ 30 | ✓ Within |
| TSS | 9 mg/L | ≤ 30 | ✓ Within |
| pH | 7.1 | 6.0 – 9.0 | ✓ Within |
| Ammonia (NH3-N) | 0.8 mg/L | ||
| Total nitrogen | 6.5 mg/L | ||
| Total phosphorus | 2.1 mg/L | ||
| Fecal coliform | 138 per 100 mL | ||
| Turbidity | 2.10 NTU |
Clarifier
ConditionScum baffle bracket corroded.
Corrective actionReplace the bracket with stainless.
Latest updateNo response recorded yet.